Page 2 - VESBO INCOLA TRIO DATA SHEET
P. 2

to be installed should be taken into consideration when connecting pipes   installation. A support  clamp  should  be  placed  right  under  the  fastening
    and fittings. In addition, extra measures should be taken to avoid external   clamp.
    forces on connection points. During installation, it is advisable not to insert
    connection  points  into  one  another  completely,  but  to  leave  a  10mm   For pipe weights to be carried easily and to avoid slipping at the connection
    allowance for pipes to expand under heat.                   points, pipe Support clamps should be used at intervals of 2m for system
                                                                safety.

    Installation                                                Clamp intervals  recommended for  vertical  and  horizontal  installations  of
                                                                VESBO INCOLA Trio pipes are listed in the table below.
    Connection of pipe and fittings
                                                                  Pipe External   Vertical Lines Max.   Horizontal Lines Max.
    VESBO INCOLA Trio pipes and fittings have belled ends equipped with   Diameter (mm)   Support Clamp Interval   Support Clamp Interval
    elastomeric  gaskets.  Applying  lubricants  on  the  gaskets  will  ease  the   OD   (mm)   10 x Pipe External
                                                                                               Diameter (mm)
    jointing. Push-fit system provides easy installations even in difficult spaces.   50   2000    500
    It is strictly not advisable to remove the gaskets during jointing.   75      2000             750
                                                                     110          2000            1100
                                                                     125          2000            1250
    Dry, unclean or cracked gaskets should not be used in an installation and   160   2000        1600
    should be replaced with new ones.
                                                                For connections between floors, short (500mm) VESBO INCOLA Trio pipes
    It is important to ensure that the ends of pipes and fittings are entirely safe   should be used. In addition, it is recommended to wrap the pipes inside
    and clean from dirt and oil before an installation.         concrete with a noise absorbing, foam-like insulation material.

    VESBO  pipes  and  fittings  are  designed  to  perform  best  as  an  integral   Connections Between Vertical and Horizontal Lines
    system and should not be mixed with pipes and fittings of other brands in
    an installation.                                            The amount of sound generated mostly depends on the length of the pipe.
                                                                For connections between vertical and horizontal lines, it is recommended
    Cutting the Pipes                                           to use two VESBO INCOLA Trio 45° Elbows instead of a single 87° Elbow.
                                                                A 25cm long VESBO INCOLA Trio pipe should be placed in between the
    VESBO INCOLA Trio pipes may be cut by using a rotary pipe cutter or a
    sharp saw that has a thin cutter head. Cracks or breaks on the cut piece   two 45° Elbows.
    must  be  carefully  checked.  Avoid  pressing  on  the  pipe  while  cutting  to
    prevent it from getting deformed.                           Installation at Horizontal Lines

    VESBO INCOLA Trio pipes should be cut at a 90° angle to the pipe axis.   It is not necessary to use the double clamping system on horizontal lines.
    After  cutting,  burrs  on  the  edges  should  be  cleaned  off.  For  ease  of   To fix pipes to the walls, it is recommended to use only pipe support clamps
    installation and to avoid slipping of the gasket, chamfering to pipe edges   right after the belled-end parts next to the joints with intervals of 10xOD (10
    (approximately15°) is recommended.                          times the external diameter of the pipe).

                                                                Installation of Pipes Inside Concrete
    Installation in Vertical Lines
                                                                Lines  in  kitchens  and  bathrooms  can  be  concealed  in  concrete.  We
    The right clamps play a crucial role in sound proofing. In vertical lines it is   recommend to wrap the lines with insulating materials in order to avoid their
    recommended to use specially designed and patented VESBO Acoustic   direct contact to concrete.
    Clamp System together with VESBO INCOLA Trio pipes and fittings for the
    best sound insulation results. VESBO Acoustic Clamp System consists of   Make  sure  that  the  lines  are  properly  aligned  and  the  joints  will  not  be
    a  double  clamping  system  comprising  a  fastening  clamp  and  a  support   disrupted while plastering.
    clamp. Specially designed air channeled rubber gasket on the fastening
    clamp prevents the sound from reaching the wall because of its vibration   Keep the installation area clean, do not leave any sharp objects that may
    absorbing  layer  by  using  the  support  clamps,  pipes  are  fixed  onto  the   damage the pipes and fittings.
    installation  wall.  It  is  advisable  to  use  a  single  VESBO  Acoustic  Clamp
    System for each floor for sound safety.

    A  fastening  clamp  should  be  placed  right  under  the  connection  point
    surrounding a pipe, and it should be locked and fixed to the pipe in a vertical